Backflow assembly test: Blue Heron Grill

Approved

Filed Nov 4, 2024 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Nov 4, 2024
Assembly type
RP
Serial number
K882952
Size
2
Test gauge serial
G-1245
Gauge calibration date
Aug 2, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-72-01118
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6619 Turkey Hill Rd
Owner: Ashby Holdings LLC
Parcel 007-72-01118