Back to the backflow review queue

Backflow assembly test: Hilltop Medical Offices

Approved

Filed Oct 15, 2025 by Jordan Pruitt, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Oct 15, 2025
Assembly type
RP
Serial number
A871316
Size
1
Test gauge serial
G-9036
Gauge calibration date
Jan 24, 2025
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 027-66-01351
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1368 Cedar Hollow Rd
Owner: Vance Holdings LLC
Parcel 027-66-01351