Back to the backflow review queue

Backflow assembly test: 3351 Old Church Way

Approved

Filed May 27, 2023 by Logan Whitcomb, Evergreen Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 27, 2023
Assembly type
DC
Serial number
Z684629
Size
3/4
Test gauge serial
G-3711
Gauge calibration date
Jul 6, 2022
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-10-01014
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3351 Old Church Way
Owner: Jamie Danner
Parcel 027-10-01014