Back to the backflow review queue

Backflow assembly test: 9568 Turkey Hill Rd

Approved

Filed Mar 14, 2026 by Cameron Danner, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 14, 2026
Assembly type
RP
Serial number
Z538303
Size
1
Test gauge serial
G-3111
Gauge calibration date
Oct 6, 2025
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Danner, current on the service date
  • All required fields present
  • Address matches parcel 027-93-01021
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9568 Turkey Hill Rd
Owner: Blake Danner
Parcel 027-93-01021