Back to the backflow review queue

Backflow assembly test: 5610 Mill Creek Ln

Approved

Filed Oct 13, 2024 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 13, 2024
Assembly type
RP
Serial number
A585619
Size
3/4
Test gauge serial
G-3821
Gauge calibration date
Feb 23, 2024
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-62-01078
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5610 Mill Creek Ln
Owner: Avery Kessler
Parcel 027-62-01078