Back to the backflow review queue

Backflow assembly test: 646 Turkey Hill Rd

Approved

Filed Apr 17, 2024 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 17, 2024
Assembly type
PVB
Serial number
K541454
Size
3/4
Test gauge serial
G-5726
Gauge calibration date
Aug 24, 2023
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-63-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

646 Turkey Hill Rd
Owner: Shawn Brandt
Parcel 027-63-01327