Backflow assembly test: 8822 Turkey Hill Dr

Approved

Filed May 8, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 8, 2026
Assembly type
RP
Serial number
K214287
Size
3/4
Test gauge serial
G-5335
Gauge calibration date
Oct 29, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-94-01145
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8822 Turkey Hill Dr
Owner: Casey Fairley
Parcel 027-94-01145