Backflow assembly test: 3877 Turkey Hill Dr

Approved

Filed Oct 15, 2025 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 15, 2025
Assembly type
DC
Serial number
Z556147
Size
3/4
Test gauge serial
G-8924
Gauge calibration date
Aug 2, 2025
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 027-93-01310
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3877 Turkey Hill Dr
Owner: Drew Fairley
Parcel 027-93-01310