Backflow assembly test: Golden Apartments
ApprovedFiled Aug 26, 2026 by Jordan Pruitt, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 26, 2026
- Assembly type
- RP
- Serial number
- B104696
- Size
- 4
- Test gauge serial
- G-9882
- Gauge calibration date
- Jan 21, 2026
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Pruitt, current on the service date
- All required fields present
- Address matches parcel 027-63-01263
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8973 Sycamore Way
Owner: Ellery Holdings LLC
Parcel 027-63-01263