Back to the backflow review queue

Backflow assembly test: Riverside Medical Offices

Approved

Filed Aug 1, 2026 by Jordan Pruitt, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 1, 2026
Assembly type
RP
Serial number
A685797
Size
4
Test gauge serial
G-7774
Gauge calibration date
Jun 24, 2026
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 027-26-01176
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

909 Quarry Trl
Owner: Brandt Holdings LLC
Parcel 027-26-01176