Back to the backflow review queue

Backflow assembly test: Two Rivers Dental

Approved

Filed Feb 19, 2024 by Avery Lindqvist, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 19, 2024
Assembly type
RP
Serial number
K947927
Size
1
Test gauge serial
G-3295
Gauge calibration date
Jul 13, 2023
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 027-12-01330
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

657 Orchard Way
Owner: Okafor Holdings LLC
Parcel 027-12-01330