Backflow assembly test: 4777 Laurel Trl
ApprovedFiled May 6, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 6, 2026
- Assembly type
- PVB
- Serial number
- K233642
- Size
- 1
- Test gauge serial
- G-3739
- Gauge calibration date
- Jan 17, 2026
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Whitcomb, current on the service date
- All required fields present
- Address matches parcel 027-77-01256
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.