Backflow assembly test: Golden Medical Offices

Approved

Filed May 11, 2024 by Avery Okafor, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 11, 2024
Assembly type
RP
Serial number
W191830
Size
4
Test gauge serial
G-7623
Gauge calibration date
Dec 9, 2023
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Okafor, current on the service date
  • All required fields present
  • Address matches parcel 027-79-01332
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.