Back to the backflow review queue
Backflow assembly test: Riverside Bakery
ApprovedFiled May 20, 2025 by Quinn Wexler, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- May 20, 2025
- Assembly type
- RP
- Serial number
- W588044
- Size
- 2
- Test gauge serial
- G-5555
- Gauge calibration date
- Oct 18, 2024
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 027-47-01334
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3125 Laurel Way
Owner: Lindqvist Holdings LLC
Parcel 027-47-01334