Back to the backflow review queue

Backflow assembly test: 3066 Fox Run Ln

Approved

Filed Sep 23, 2025 by Taylor Ramirez, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 23, 2025
Assembly type
RP
Serial number
W231049
Size
3/4
Test gauge serial
G-2559
Gauge calibration date
Feb 20, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 025-32-01170
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3066 Fox Run Ln
Owner: Shawn Nguyen
Parcel 025-32-01170