Backflow assembly test: 8575 Laurel Rd
ApprovedFiled Jul 30, 2025 by Jordan Vance, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 30, 2025
- Assembly type
- RP
- Serial number
- Z443212
- Size
- 1
- Test gauge serial
- G-2880
- Gauge calibration date
- Mar 27, 2025
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 025-47-01254
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.