Back to the backflow review queue
Backflow assembly test: 6396 Turkey Hill Ln
ApprovedFiled Sep 22, 2026 by Cameron Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 22, 2026
- Assembly type
- RP
- Serial number
- A450711
- Size
- 3/4
- Test gauge serial
- G-1403
- Gauge calibration date
- Apr 11, 2026
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Danner, current on the service date
- All required fields present
- Address matches parcel 025-90-01299
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6396 Turkey Hill Ln
Owner: Reese Benton
Parcel 025-90-01299