Backflow assembly test: 6396 Turkey Hill Ln
ApprovedFiled Sep 28, 2025 by Sam Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 28, 2025
- Assembly type
- RP
- Serial number
- A450711
- Size
- 3/4
- Test gauge serial
- G-2911
- Gauge calibration date
- Feb 18, 2025
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Nguyen, current on the service date
- All required fields present
- Address matches parcel 025-90-01299
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.