Back to the backflow review queue
Backflow assembly test: 8485 Turkey Hill Dr
ApprovedFiled Sep 2, 2025 by Cameron Danner, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 2, 2025
- Assembly type
- DC
- Serial number
- K719360
- Size
- 3/4
- Test gauge serial
- G-4177
- Gauge calibration date
- Apr 5, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Danner, current on the service date
- All required fields present
- Address matches parcel 025-90-01175
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8485 Turkey Hill Dr
Owner: Taylor Calloway
Parcel 025-90-01175