Backflow assembly test: 1163 Cedar Hollow Ct
ApprovedFiled Dec 9, 2023 by Riley Nguyen, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 9, 2023
- Assembly type
- PVB
- Serial number
- A136562
- Size
- 1
- Test gauge serial
- G-4650
- Gauge calibration date
- Aug 5, 2023
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Nguyen, current on the service date
- All required fields present
- Address matches parcel 025-88-01057
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.