Back to the backflow review queue

Backflow assembly test: 9075 Laurel Dr

Approved

Filed Apr 1, 2024 by Sam Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 1, 2024
Assembly type
RP
Serial number
W601489
Size
3/4
Test gauge serial
G-9046
Gauge calibration date
Oct 23, 2023
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 025-25-01309
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9075 Laurel Dr
Owner: Taylor Stroud
Parcel 025-25-01309