Backflow assembly test: Two Rivers Self Storage
ApprovedFiled Feb 22, 2026 by Cameron Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 22, 2026
- Assembly type
- RP
- Serial number
- B493426
- Size
- 4
- Test gauge serial
- G-4442
- Gauge calibration date
- Nov 19, 2025
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Danner, current on the service date
- All required fields present
- Address matches parcel 025-44-01017
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.