Backflow assembly test: 7759 Mill Creek Ln
ApprovedFiled Dec 16, 2025 by Sam Nguyen, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 16, 2025
- Assembly type
- PVB
- Serial number
- K585859
- Size
- 3/4
- Test gauge serial
- G-2513
- Gauge calibration date
- Jun 8, 2025
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Nguyen, current on the service date
- All required fields present
- Address matches parcel 025-92-01136
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
7759 Mill Creek Ln
Owner: Jamie Ashby
Parcel 025-92-01136