Back to the backflow review queue
Backflow assembly test: Golden Self Storage
ApprovedFiled Aug 1, 2025 by Riley Nguyen, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 1, 2025
- Assembly type
- RP
- Serial number
- Z380413
- Size
- 4
- Test gauge serial
- G-9409
- Gauge calibration date
- Jul 2, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Nguyen, current on the service date
- All required fields present
- Address matches parcel 025-22-01279
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9830 Turkey Hill Dr
Owner: Nguyen Holdings LLC
Parcel 025-22-01279