Backflow assembly test: 6236 Meadow Lark Ct

Approved

Filed Apr 3, 2025 by Reese Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 3, 2025
Assembly type
PVB
Serial number
Z903832
Size
1
Test gauge serial
G-9002
Gauge calibration date
Oct 13, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 025-44-01074
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.