Back to the backflow review queue

Backflow assembly test: 7446 Ridgeview Way

Approved

Filed Jun 23, 2024 by Reese Calloway, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 23, 2024
Assembly type
RP
Serial number
B831413
Size
1
Test gauge serial
G-7954
Gauge calibration date
Mar 4, 2024
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Calloway, current on the service date
  • All required fields present
  • Address matches parcel 025-28-01183
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7446 Ridgeview Way
Owner: Reese Wexler
Parcel 025-28-01183