Back to the backflow review queue

Backflow assembly test: 7761 Sycamore Trl

Approved

Filed Jun 12, 2025 by Alex Ashby, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 12, 2025
Assembly type
RP
Serial number
A463187
Size
1
Test gauge serial
G-1453
Gauge calibration date
Oct 31, 2024
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Ashby, current on the service date
  • All required fields present
  • Address matches parcel 021-84-01353
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7761 Sycamore Trl
Owner: Parker Hollins
Parcel 021-84-01353