Back to the backflow review queue
Backflow assembly test: 2065 Meadow Lark Rd
ApprovedFiled Nov 22, 2024 by Riley Pruitt, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 22, 2024
- Assembly type
- RP
- Serial number
- B326219
- Size
- 3/4
- Test gauge serial
- G-2278
- Gauge calibration date
- Apr 5, 2024
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Pruitt, current on the service date
- All required fields present
- Address matches parcel 021-22-01149
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2065 Meadow Lark Rd
Owner: Jordan Vance
Parcel 021-22-01149