Back to the backflow review queue

Backflow assembly test: Main Street Taqueria

Approved

Filed Jun 26, 2026 by Parker Ramirez, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 26, 2026
Assembly type
RP
Serial number
A998858
Size
1
Test gauge serial
G-6271
Gauge calibration date
Oct 14, 2025
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 021-58-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2798 Quarry Ct
Owner: Okafor Holdings LLC
Parcel 021-58-01147