Back to the backflow review queue

Backflow assembly test: 6415 Quarry Rd

Approved

Filed Nov 8, 2026 by Riley Pruitt, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 8, 2026
Assembly type
DC
Serial number
Z480151
Size
3/4
Test gauge serial
G-5333
Gauge calibration date
Aug 26, 2026
Check valve 1
0.9 psid
Check valve 1 closed tight
No
Check valve 2
3.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 021-64-01332
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6415 Quarry Rd
Owner: Taylor Ellery
Parcel 021-64-01332