Back to the backflow review queue

Backflow assembly test: Station Bakery

Approved

Filed Aug 16, 2026 by Riley Pruitt, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 16, 2026
Assembly type
RP
Serial number
A312326
Size
2
Test gauge serial
G-2631
Gauge calibration date
Jan 6, 2026
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 021-83-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4004 Hickory Ct
Owner: Lindqvist Holdings LLC
Parcel 021-83-01224