Back to the backflow review queue

Backflow assembly test: Station Bakery

Approved

Filed Jul 12, 2025 by Avery Ramirez, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jul 12, 2025
Assembly type
RP
Serial number
A312326
Size
2
Test gauge serial
G-2499
Gauge calibration date
Aug 3, 2024
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
4 psid
Relief valve opened at
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 021-83-01224
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4004 Hickory Ct
Owner: Lindqvist Holdings LLC
Parcel 021-83-01224