Backflow assembly test: 9103 Orchard Trl
ApprovedFiled May 18, 2025 by Hayden Stroud, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- May 18, 2025
- Assembly type
- RP
- Serial number
- W247015
- Size
- 1
- Test gauge serial
- G-3936
- Gauge calibration date
- Mar 24, 2025
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Stroud, current on the service date
- All required fields present
- Address matches parcel 019-97-01009
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9103 Orchard Trl
Owner: Reese Whitcomb
Parcel 019-97-01009