Back to the backflow review queue

Backflow assembly test: 9103 Orchard Trl

Approved

Filed Apr 10, 2023 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Apr 10, 2023
Assembly type
RP
Serial number
W247015
Size
1
Test gauge serial
G-1090
Gauge calibration date
Feb 15, 2023
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-97-01009
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9103 Orchard Trl
Owner: Reese Whitcomb
Parcel 019-97-01009