Backflow assembly test: 9103 Orchard Trl
ApprovedFiled Apr 10, 2023 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Apr 10, 2023
- Assembly type
- RP
- Serial number
- W247015
- Size
- 1
- Test gauge serial
- G-1090
- Gauge calibration date
- Feb 15, 2023
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Brandt, current on the service date
- All required fields present
- Address matches parcel 019-97-01009
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9103 Orchard Trl
Owner: Reese Whitcomb
Parcel 019-97-01009