Back to the backflow review queue
Backflow assembly test: 6335 Meadow Lark Dr
ApprovedFiled Sep 9, 2026 by Hayden Stroud, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 9, 2026
- Assembly type
- RP
- Serial number
- A285798
- Size
- 1
- Test gauge serial
- G-3750
- Gauge calibration date
- Jan 16, 2026
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2 psid
- Relief valve opened at
- 4.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Stroud, current on the service date
- All required fields present
- Address matches parcel 019-42-01065
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6335 Meadow Lark Dr
Owner: Jamie Stroud
Parcel 019-42-01065