Backflow assembly test: 2964 Fox Run Trl

Approved

Filed Sep 1, 2025 by Jamie Pruitt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Sep 1, 2025
Assembly type
RP
Serial number
W544946
Size
3/4
Test gauge serial
G-6094
Gauge calibration date
Nov 28, 2024
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.8 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 019-82-01097
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2964 Fox Run Trl
Owner: Hayden Nguyen
Parcel 019-82-01097