Back to the backflow review queue

Backflow assembly test: 2964 Fox Run Trl

Approved

Filed Sep 20, 2023 by Logan Vance, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Sep 20, 2023
Assembly type
RP
Serial number
W544946
Size
3/4
Test gauge serial
G-4493
Gauge calibration date
Jun 13, 2023
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 019-82-01097
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2964 Fox Run Trl
Owner: Hayden Nguyen
Parcel 019-82-01097