Backflow assembly test: Riverside Dental

Approved

Filed Apr 29, 2024 by Taylor Wexler, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Apr 29, 2024
Assembly type
RP
Serial number
B945790
Size
1 1/2
Test gauge serial
G-6422
Gauge calibration date
Nov 1, 2023
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Wexler, current on the service date
  • All required fields present
  • Address matches parcel 019-66-01246
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.