Back to the backflow review queue

Backflow assembly test: 9803 Spring Branch Way

Approved

Filed Dec 28, 2025 by Sam Brandt, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 28, 2025
Assembly type
DC
Serial number
W447642
Size
1
Test gauge serial
G-6652
Gauge calibration date
Oct 13, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-71-01077
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9803 Spring Branch Way
Owner: Jamie Ramirez
Parcel 019-71-01077