Backflow assembly test: Riverside Animal Hospital
ApprovedFiled Aug 16, 2024 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 16, 2024
- Assembly type
- DC
- Serial number
- K947960
- Size
- 1 1/2
- Test gauge serial
- G-5853
- Gauge calibration date
- May 27, 2023
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Brandt, current on the service date
- All required fields present
- Address matches parcel 019-28-01276
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1017 Turkey Hill Ln
Owner: Whitcomb Holdings LLC
Parcel 019-28-01276