Back to the backflow review queue

Backflow assembly test: Hilltop Dental

Approved

Filed Oct 26, 2026 by Sam Brandt, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Oct 26, 2026
Assembly type
RP
Serial number
Z381331
Size
2
Test gauge serial
G-7171
Gauge calibration date
Sep 14, 2026
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 019-19-01142
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2128 Old Church Way
Owner: Ellery Holdings LLC
Parcel 019-19-01142