Back to the backflow review queue

Backflow assembly test: 3521 Stone Gate Ct

Approved

Filed Oct 12, 2026 by Hayden Stroud, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Oct 12, 2026
Assembly type
RP
Serial number
W939117
Size
3/4
Test gauge serial
G-8398
Gauge calibration date
Mar 24, 2026
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 019-56-01187
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3521 Stone Gate Ct
Owner: Drew Hollins
Parcel 019-56-01187