Back to the backflow review queue

Backflow assembly test: Golden Medical Offices

Approved

Filed Oct 29, 2026 by Hayden Danner, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 29, 2026
Assembly type
RP
Serial number
B864595
Size
1
Test gauge serial
G-1163
Gauge calibration date
Apr 20, 2026
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 013-43-01269
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3877 Stone Gate Ln
Owner: Benton Holdings LLC
Parcel 013-43-01269