Back to the backflow review queue
Backflow assembly test: 9336 Old Church Way
ApprovedFiled Mar 27, 2026 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 27, 2026
- Assembly type
- RP
- Serial number
- A947854
- Size
- 3/4
- Test gauge serial
- G-6998
- Gauge calibration date
- Jun 27, 2025
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Benton, current on the service date
- All required fields present
- Address matches parcel 013-78-01035
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9336 Old Church Way
Owner: Jamie Harlow
Parcel 013-78-01035