Back to the backflow review queue
Backflow assembly test: Riverside Dental
ApprovedFiled Feb 25, 2026 by Jamie Harlow, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Feb 25, 2026
- Assembly type
- RP
- Serial number
- A511075
- Size
- 2
- Test gauge serial
- G-8951
- Gauge calibration date
- Nov 3, 2024
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Harlow, current on the service date
- All required fields present
- Address matches parcel 013-28-01067
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1793 Stone Gate Rd
Owner: Marsh Holdings LLC
Parcel 013-28-01067