Back to the backflow review queue
Backflow assembly test: 7986 Quarry Rd
ApprovedFiled Sep 4, 2023 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 4, 2023
- Assembly type
- RP
- Serial number
- W637377
- Size
- 3/4
- Test gauge serial
- G-8280
- Gauge calibration date
- Mar 20, 2023
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Benton, current on the service date
- All required fields present
- Address matches parcel 013-85-01328
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
7986 Quarry Rd
Owner: Shawn Harlow
Parcel 013-85-01328