Back to the backflow review queue

Backflow assembly test: Riverside Car Wash

Approved

Filed Oct 10, 2025 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 10, 2025
Assembly type
RP
Serial number
A999823
Size
2
Test gauge serial
G-9467
Gauge calibration date
Mar 16, 2025
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-59-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2439 Spring Branch Trl
Owner: Kessler Holdings LLC
Parcel 013-59-01224