Backflow assembly test: 3306 Turkey Hill Ct

Approved

Filed Jan 14, 2026 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 14, 2026
Assembly type
PVB
Serial number
A491959
Size
1
Test gauge serial
G-3875
Gauge calibration date
Sep 28, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-19-01270
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.