Backflow assembly test: 3037 Ridgeview Trl

Approved

Filed Nov 7, 2026 by Hayden Danner, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 7, 2026
Assembly type
RP
Serial number
Z121745
Size
3/4
Test gauge serial
G-9871
Gauge calibration date
Aug 7, 2026
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 013-19-01102
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.