Backflow assembly test: 4413 Quarry Ln
ApprovedFiled Jul 25, 2026 by Hayden Danner, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 25, 2026
- Assembly type
- RP
- Serial number
- K937785
- Size
- 3/4
- Test gauge serial
- G-4841
- Gauge calibration date
- May 31, 2026
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 013-46-01342
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4413 Quarry Ln
Owner: Casey Ellery
Parcel 013-46-01342